The MD Infotech SCADA/RTU sends your wind or solar plant's data to the Tamil Nadu SLDC and SRLDC over IEC 60870‑5‑104 — unprocessed, time-stamped and tested end to end with the SLDC.

How it works

From the plant to the Tamil Nadu SLDC, unprocessed

Grid-connected wind and solar plants have to stream real-time telemetry to the State or Regional Load Despatch Centre under the CEA connectivity standards and the Indian Electricity Grid Code. MD Infotech supplies its own SCADA/RTU, which reads the field directly and sends the values unprocessed, as the Tamil Nadu SLDC requires. We also map the signals, set up the main and standby links, and stay with the plant through end-to-end testing with the SLDC/RLDC until it is live.

PLANT → SLDC / RLDC · IEC 60870-5-104 TELEMETRY PATH LINK UP
PLANT SITE · INSIDE THE FENCE WAN LOAD DESPATCH MAIN STANDBY ISTS ICCP/TASE.2 Wind turbines all OEM controllers Solar inverters inverters · WMS Turbine meters ABT meter · MFM · CB MD INFOTECH SCADA / RTU Direct acquisition meters · CB · WTG Raw values no processing IEC 104 server TCP 2404 values sent exactly as measured source timestamps · quality bits · hot standby Firewall VPN · ACL SLDC State Load Despatch Centre e.g. Tamil Nadu SLDC EMS / SCADA · FEP controlling station RLDC Regional Load Despatch Centre e.g. SRLDC → NLDC direct for ISTS plants Unprocessed values to the SLDC · point list & IOA map agreed with the SLDC

← swipe to see the full path →

Telemetry: MW, MVAr, kV, Hz, CB status, met data From LDC: interrogation, clock sync, set points Standby channel: VSAT / 4G VPN ISTS-connected plants report to RLDC

Typical signal list

SignalIEC 104 typeSent as
Active power, MWM_ME_NC_1 · 13Spontaneous on deadband, plus cyclic
Reactive power, MVArM_ME_NC_1 · 13Spontaneous, plus cyclic
Bus voltage kV, frequency HzM_ME_NC_1 · 13Spontaneous, plus cyclic
Breaker & isolator statusM_DP_TB_1 · 31Spontaneous, time-tagged
Wind speed, irradiance, ambient tempM_ME_NC_1 · 13Cyclic
Available capacity, units onlineM_ME_NC_1 · 13Cyclic
Energy import / export, MWhM_IT_TB_1 · 37Counter interrogation
Power set point, if the LDC issues oneC_SE_NC_1 · 50Command, LDC → plant

The final point list, IOA addresses, deadbands and scaling are agreed with your SLDC/RLDC before end-to-end testing.

What the link carries, frame by frame

MD RTU 10.0.0.20:2404 ⇄ TN SLDC FEPLIVE
Illustrative frame trace · simulated values
TCP 2404 k = 12 · w = 8 t1 15s · t2 10s · t3 20s CP56Time2a time tags Redundant connections GPS / NTP time sync LDC IP whitelisting TLS (IEC 62351-3) where supported

Tamil Nadu SLDC integration for wind and solar plants

The Tamil Nadu State Load Despatch Centre (TN SLDC), operated by TANTRANSCO, needs live data from every grid-connected wind and solar plant in the state — often still called EB SLDC data sharing from the TNEB days. MD Infotech connects plants across the state's wind belts — Tirunelveli, Thoothukudi, Coimbatore, Tiruppur, Theni and Kanyakumari — to the TN SLDC with the MD Infotech SCADA/RTU sending unprocessed IEC 60870‑5‑104 data, a point list in the SLDC's format and a main plus standby communication link.

Plants connected to the inter-state network share the same real-time data with the Southern Regional Load Despatch Centre (SRLDC). One SCADA/RTU can feed both the SLDC and the RLDC where the connection agreement asks for it.

An MD Infotech SCADA/RTU at each turbine sends unprocessed IEC 104 data directly to the SLDC.
Who it's for

Wind farm owners, solar park developers and O&M companies with a Tamil Nadu SLDC or SRLDC data-sharing requirement.

Any turbine make or model

The RTU reads each controller directly, so every make and model in our fleet list can report to the SLDC, plus solar inverters of any make.

Existing plants too

Older wind farms without telemetry can be brought onto the SLDC link without changing the OEM controller program.

SLDC-ready for every make and model

SLDC/RLDC data sharing isn't limited to a few brands. If we provide SCADA for your turbines, the MD Infotech SCADA/RTU can send their data to the SLDC as well, including older and lower-capacity models.

Suzlon S52–S144Vestas V27–V100RRB V47Siemens Gamesa G52–G126GE 1.5 / 2.xInox DF 93.3 / 100 / 113Leitwind LTW77 / 80Kenersys K82NEG Micon NM48Enercon / Wind World E-40–E-82Senvion MM82–MM100Regen Vensys 77 / 82 / 87Envision EN-115 / 131Acciona AW3000 · NordexAdani Wind 3.3 / 5.2 MWWinWinD WWD-1NEPC 225–400 kWPioneer WinconMitsubishi MWTSolar inverters · all makes
01

Signal list & IOA map

We draft the point list in the SLDC/RLDC's format and agree addresses, scaling and deadbands with them.

02

SCADA/RTU & dual links

An MD Infotech SCADA/RTU at each turbine, sending raw values directly to the SLDC over a main and a standby channel behind a firewall.

03

End-to-end testing

Point-by-point checks with the LDC control room, so every value, status and timestamp is verified on their EMS.

04

Go-live & link watch

Our desk monitors link health around the clock and raises an alarm the moment the LDC connection drops.

All over India

Load despatch centres across India

The same MD Infotech SCADA/RTU and IEC 60870‑5‑104 link works for wind and solar plants reporting to any State or Regional Load Despatch Centre.

Tamil Nadu SLDCGujarat SLDCKarnataka SLDCMaharashtra SLDCRajasthan SLDCAndhra Pradesh SLDCTelangana SLDCMadhya Pradesh SLDCKerala SLDCSRLDCWRLDCNRLDCERLDC

FAQ

Common questions

How do wind farms in Tamil Nadu share real-time data with the Tamil Nadu SLDC?

An MD Infotech SCADA/RTU at each turbine reads the turbine controller and its meter and sends live, unprocessed MW, MVAr, voltage, frequency, status and wind data directly to the Tamil Nadu State Load Despatch Centre (operated by TANTRANSCO) over IEC 60870-5-104, on a main fibre or MPLS link with a VSAT or 4G standby.

Why does the TN SLDC need unprocessed data?

The Tamil Nadu SLDC needs plant data exactly as measured, with source timestamps. The MD Infotech SCADA/RTU sends every value unprocessed over IEC 60870-5-104.

Can you share real-time data with SRLDC?

Yes. Plants connected to the inter-state transmission system report to the Southern Regional Load Despatch Centre (SRLDC). One MD Infotech SCADA/RTU can feed both SLDC and RLDC where required.

Which turbine makes and models can share data with the SLDC?

All of them: Suzlon, Vestas, RRB, Siemens Gamesa, GE, Inox, Leitwind, Kenersys, NEG Micon, Enercon / Wind World, Senvion, Regen Powertech, Envision, Acciona, Nordex, Adani Wind, WinWinD, NEPC, Pioneer Wincon and Mitsubishi, plus solar inverters of any make.

Do you work with SLDCs outside Tamil Nadu?

Yes. The same IEC 60870-5-104 SCADA/RTU approach works with State Load Despatch Centres in Gujarat, Karnataka, Maharashtra, Rajasthan, Andhra Pradesh, Telangana, Madhya Pradesh and other states, and with the regional RLDCs.

Is TNEB SLDC the same as Tamil Nadu SLDC?

Yes. Many site teams still call it TNEB SLDC or EB SLDC. Today the Tamil Nadu SLDC is operated by TANTRANSCO, and our SCADA/RTU meets its real-time data requirements.

How long does SLDC integration take?

It depends on the plant and the SLDC test schedule. The steps are signal list approval, RTU and link installation, end-to-end point testing with the SLDC, then go-live.

Talk to us

Bring your fleet onto one SCADA platform

Tell us the turbine count, OEM mix and site location and we'll scope a network design and integration plan.